Abstract:
Feasible zone on indoor cooling designing state point of capillary mat radiant air conditioning system for residence buildings is analyzed, comprehensively considering with following factors: radiant heat exchange, clothing thermal resistance and individuals' metabolic profile. When indoor design dry bulb temperature is set to 26~27 ℃ and indoor design specific humidity is set to
12.0 g/kg, the design status is in the level I thermal comfort zone, meanwhile good energy saving effect is obtained. Room temperature at night is recommended to set to 28~30 ℃ by presetting temperature controllers, so as to adapt to the metabolism level and clothing situation.
HE Zhong-kai1,GAO Qiang2,JIAO Jia-hai1 et al. Feasible Zone Analysis on Indoor Cooling Designing State Point of Capillary Mat Radiant Air Conditioning System for Healthy Housing[J]. Architecture Technology, 2018, 49(4): 411-.