Comparative analysis of radiant floor heating and radiator heating
TANG Wen1, ZHOU Jun-ming2, PENG Dong-gen2
1. Nanchang Architectural Design Institute, 330031, Nanchang, China; 2. School of Civil Engineering and Architecture,
Nanchang university, 330031, Nanchang, China
Abstract:
A physical model of radiant floor heating room south, using the known conditions for radiant floor heating room to build mathematical model, model calculation results obtained floor room with radiant surface temperature, indoor air temperature and PMV, through adjustment of the plate surface temperature obtained when the floor temperature of 26°C indoor heat environment and most comfortable. Under the same physical model of the radiant floor heating and radiator heating are compared, the comparative analysis that the average air temperature radiator heating room than the low temperature radiant floor heating room high 0.87 ~ 0.95°C.